h1. Station sous pointe Karl Süss AP6 

 {{toc}} 

 h2. KSAP6 

 [[karl_suss_ap6_console:]] 

 h2. AP6 Châssis 

 !clipboard-202306230939-wk2di.png! 

 !clipboard-202202241549-ibnh1.png! 

 !clipboard-202110251012-p94w0.png! 

 *J12 ♂ (mâle) 
 J22 ♀ (femelle)* 

 h2. Contrôleur 

 !clipboard-202110181528-f7ndu.png! 
 210AA071-01 

 !clipboard-202111020930-gbcne.png! 

 h3. 260PC113 Karl Suss 16 Channel Input Card 

 !clipboard-202110291053-irhn6.png! 
 260PC113 Karl Suss 16 Channel Input Card 

 

 | | BROCHE | ||BROCHE| | BROCHE | ||BROCHE| 
 | DB25 | 1 | *GND* |J22| 20| DB25 | 14 |    |J22|29| 
 | DB25 | 2 | |J22| 27 | DB25 | 15 | *GND* |J22|18| 
 | DB25 | 3 | |J22| 25| DB25 | 16 |    |J22|23| 
 | DB25 | 4 | *GND* |J22| 16| DB25 | 17 |    |J22|21| 
 | DB25 | 5 | |J22| 19 | DB25 | 18 | *GND* |J22|14| 
 | DB25 | 6 | NC || | DB25 | 19 |    | *J12* |2| 
 | DB25 | 7 | *GND* |J22| 12| DB25 | 20 |    |J22|17| 
 | DB25 | 8 | |J22| 15 | DB25 | 21 | *GND* | J22 |10| 
 | DB25 | 9 | |J22| 13 | DB25 | 22 |    |J22|11| 
 | DB25 | 10 | *GND EYF* |J22| 8 | DB25 | 23 | *EYF* |J22|7| 
 | DB25 | 11 | |J22| 9 | DB25 | 24 | *GND* |J22|6| 
 | DB25 | 12 | |J22| 3 | DB25 | 25 |    |J22|5| 
 | DB25 | 13 | *GND* |J22| 4| 

 h3. 260PC152 Karl Suss VALVE 16 sorties 

 !clipboard-202110291614-h8car.png! 

 h2. Connecteurs 

 !clipboard-202110191431-ftq3o.png! 
 !clipboard-202110191504-p6tbi.png! 
 Male vue de dessus 
 Sub-D FCI 50 

 !clipboard-202110291524-y1awq.png! 

 h3. J12 ♂ (mâle) 
 Connecteur Sub-D Mâle RS PRO 50 voies Traversant Droit 
 Code commande RS: 
     528-3581 
 https://fr.rs-online.com/web/p/connecteurs-sub-d/5283581 

 | | BROCHE | | | BROCHE | | | BROCHE | | 
 | J12 | 1 | AU | J12 | 18 | Moteur axe Y B- | J12 | 34 |    | 
 | J12 | 2 | DOOR | J12 | 19 | Moteur axe Y B+ | J12 | 35 | VACUUM | 
 | J12 | 3 | Moteur axe X A+ | J12 | 20 | Moteur axe Y B+ | J12 | 36 |    | 
 | J12 | 4 | Moteur axe X A+ | J12 | 21 |    | J12 | 37 |    | 
 | J12 | 5 | Moteur axe X A- | J12 | 22 |    | J12 | 38 |    | 
 | J12 | 6 | Moteur axe X A- | J12 | 23 | Moteur axe Z A+ | J12 | 39 |    | 
 | J12 | 7 | Moteur axe X B+ | J12 | 24 | Moteur axe Z A- | J12 | 40 |    | 
 | J12 | 8 | Moteur axe X B+ | J12 | 25 | Moteur axe Z B+ | J12 | 41 |    | 
 | J12 | 9 | Moteur axe X B- | J12 | 26 | Moteur axe Z B- | J12 | 42 |    | 
 | J12 | 10 | Moteur axe X B- | J12 | 27 | Moteur Theta A+ | J12 | 43 |    | 
 | J12 | 11 |    | J12 | 28 | Moteur Theta A- | J12 | 44 |    | 
 | J12 | 12 |    | J12 | 29 | Moteur Theta B+ | J12 | 45 | GND | 
 | J12 | 13 | Moteur axe Y A+ | J12 | 30 | Moteur Theta B- | J12 | 46 | GND | 
 | J12 | 14 | Moteur axe Y A+ | J12 | 31 | VACUUM | J12 | 47 | GND | 
 | J12 | 15 | Moteur axe Y A- | J12 | 32 |    | J12 | 48 | GND | 
 | J12 | 16 | Moteur axe Y A- | J12 | 33 |    | J12 | 49 | GND DOOR| 
 | J12 | 17 | Moteur axe Y B- |    |    |    | J12 | 50 | AU | 

 h3. J22 ♀ (femelle) 

 Connecteur Sub-D Femelle RS PRO 50 voies Traversant Droit 

 Code commande RS: 
     528-3648 
 https://fr.rs-online.com/web/p/connecteurs-sub-d/5283648 


 | | BROCHE | | | BROCHE | | | BROCHE | | 
 | J22 | 1 | NC | J22 | 18 | *GND* | J22 | 34 | NC | 
 | J22 | 2 | NC | J22 | 19 |    | J22 | 35 | NC | 
 | J22 | 3 | EXL | J22 | 20 | *GND* | J22 | 36 | NC | 
 | J22 | 4 | *GND* | J22 | 21 |    | J22 | 37 | NC | 
 | J22 | 5 | EXR | J22 | 22 | *GND* | J22 | 38 | NC | 
 | J22 | 6 | *GND* | J22 | 23 |    | J22 | 39 | NC | 
 | J22 | 7 | EYF | J22 | 24 | *GND* | J22 | 40 | NC | 
 | J22 | 8 | *GND* EYF | J22 | 25 |    | J22 | 41 | NC | 
 | J22 | 9 | EYB | J22 | 26 | *GND* | J22 | 42 | NC | 
 | J22 | 10 | *GND* | J22 | 27 |    | J22 | 43 | NC | 
 | J22 | 11 | EZup | J22 | 28 | *GND* | J22 | 44 | NC | 
 | J22 | 12 | *GND* | J22 | 29 |    | J22 | 45 | NC | 
 | J22 | 13 | EZdn | J22 | 30 | *GND* | J22 | 46 | NC | 
 | J22 | 14 | *GND* | J22 | 31 | NC | J22 | 47 | +5V | 
 | J22 | 15 | ETcw | J22 | 32 | NC | J22 | 48 | +5V | 
 | J22 | 16 | *GND* | J22 | 33 | NC | J22 | 49 | +5V | 
 | J22 | 17 | ETccw |    |    |    | J22 | 50 | +5V | 

 h2. Capteur fin de course 

 !clipboard-202110251609-uyvvh.png! 
 fourche optique Honeywell S-180-B55 

 !clipboard-202110280935-peqaw.png! 

 !clipboard-202110280947-by0u2.png! 
 *E* Emetteur (diode) *D* Détecteur (phototransistor) 

 !clipboard-202110280958-0w6t2.png! 

 !clipboard-202111031634-76wfu.png! 

 

 h2. boitier 

 h3. MKS 

 h4. entretoise 

 !clipboard-202401241348-o6oqy.png! 
 Entretoise filetée Wurth Elektronik, longueur 70mm, Mâle / Femelle, M3 
 Wurth Elektronik 

 Code commande RS: 
     176-8231 
 Référence fabricant: 
     971700321 
 Marque: 
     Wurth Elektronik 


 h2. Alimentations 

 h3. Connecteur IEC filtré Mâle Schurter 

 !clipboard-202306270927-fxcxx.png! 

 Connecteur IEC filtré Mâle Schurter, 4A, 250 V c.a., Montage panneau 

 Code commande RS: 
     493-2973 
 Référence fabricant: 
     4304.4003 
 Marque: 
     Schurter 

 h3. Fusible 

 Cartouche fusible SIBA GZ, 250mA 5 x 20mm Type T 250V c.a. 
 SIBA 

 Code commande RS: 
     783-3270 
 Référence fabricant: 
     70-007-65/0.25A 
 Marque: 
     SIBA 

 h3. 12V 

 !clipboard-202401231044-uisue.png! 

 Alimentation pour rail DIN RS PRO, 12Vout 2A, 120 → 370 V dc, 85 → 264 V acin, 24W 
 RS PRO 

 RS Stock No.: 
     190-4191 
 Brand: 
     RS PRO 

 !clipboard-202306270928-omvpu.png! 

 Alimentation à découpage, TRACOPOWER, TXL 25W, 1 sortie à 12V c.c. 2.1A 

 Code commande RS: 
     449-3119 
 Référence fabricant: 
     TXL 025-12S 
 Marque: 
     TRACOPOWER 

 h3. 5V  

 !clipboard-202401231041-z7qik.png! 

 Alimentation pour rail DIN RS PRO, 5Vout 3A, 120 → 370 V dc, 85 → 264V c.a.in, 15W 
 RS PRO 

 RS Stock No.: 
     190-4190 
 Brand: 
     RS PRO 



 Alimentation à découpage, TRACOPOWER, TXL 25W, 1 sortie à 5V c.c. 5A 

 Code commande RS: 
     449-3096 
 Référence fabricant: 
     TXL 025-05S 
 Marque: 
     TRACOPOWER 

 h3. Contacteur AU 

 bobine 12vcc 

 contact NO 12vcc 

 Contacteur Finder série 22 Series, 2 pôles , 25 A, 12 V c.a./c.c. 
 Finder 

 RS Stock No.: 
     789-2705 
 Mfr. Part No.: 
     22.32.0.012.4320 
 Brand: 
     Finder 

 h3. câblage 

 !clipboard-202306271425-zuytn.png! 

 

 h2. Moteurs 

 Theta et Axe Z 

 !clipboard-202110191422-xp8dx.png! 
 ESCAP P520 254 0.7 60 

 h4. courant dans le moteur theta 

 !clipboard-202112141554-gyzwb.png! 
 driver DRV8825 Vref=1V    alim 12V 2.1A TXL025-12S 

 h4. courant dans le moteur Z 

 !clipboard-202112141613-pinip.png! 
 driver DRV8825 Vref=1V    alim 12V 2.1A TXL025-12S GRBL $102=3208 steps/mm $122=50 Acceleration, mm/sec^2 CMD g01 z0.2 f25 

 !clipboard-202112141623-lt2pk.png! 
 $122=1 Acceleration, mm/sec^2 

 !clipboard-202112141624-9s0bw.png! 
 $122=0.1 Acceleration, mm/sec^2 

 h4. moteur X 

 !clipboard-202112141644-xoaye.png! 
 $120=5 Acceleration, mm/sec^2 GRBL $100=3208 steps/mm CMD g01 X-10 f100 

 h4. moteur Y 

 !clipboard-202112141644-bzf97.png! 
 $121=5 Acceleration, mm/sec^2 GRBL $101=3208 steps/mm CMD g01 y-10 f100 

 h3. Nouveau câblage 

 !clipboard-202110251302-x7174.png! 
 câble moteur AWG23 (0.25mm²,67mOhms/m,) 

 

 h3. Nouveau contrôleur    axe Z et Theta 

 DRV8825 Stepper Motor Driver 

 !clipboard-202312211420-bxs42.png! 

 !clipboard-202110251411-xrnym.png! 

 !clipboard-202204121547-urv2h.png! 
 drv8825 microstepping jumpers 

 https://reprap.org/wiki/RAMPS_1.4 

 

 h3. Nouveau contrôleur axe X et Y 

 !clipboard-202110251328-xl46h.png! 
 TB6600 4A DC 9-42V 
 !clipboard-202110251326-hfzhq.png! 

 Driver Trinamic  
 https://www.trinamic.com/ 
 !clipboard-202111061329-yv8kp.png! 

 h3. Filtre (Smoother Stepper) 

 lorsque le moteur se déplace lentement(100 mm/min feedrate) 

 !clipboard-202111061416-iuckh.png! 

 !clipboard-202111061406-cuuvc.png! 

 !clipboard-202111061403-gr9r1.png! 

 !clipboard-202111061404-adt61.png! 

 http://birkbinnard.com/blog/smoothing-stepper-motor-movement/ 
 https://cabristor.blogspot.com/2015/02/drv8825-missing-steps.html 

 h2. Logiciel pilotage 4 axes 

 https://github.com/zapmaker/GrblHoming/releases/tag/v3.6.1 
 Grbl Controller 3.61 de zapmaker pour Windows 

 https://github.com/terjeio/ioSender 
 https://github.com/terjeio/ioSender/wiki 
 ioSender - a gcode sender for grblHAL or grbl 

 https://github.com/fra589/grbl-Mega-5X 
 Grbl pour Arduino Mega2560 5 axes 

 https://github.com/gnea/grbl/wiki 
 wiki grbl 

 h3. cpu_map.h - CPU and pin mapping configuration file Part of Grbl 

 X Step - Pin A0 
 Y Step - Pin A6 
 Z Step - Pin D46 
 A Step - Pin D26 

 X Dir - Pin A1 
 Y Dir - Pin A7 
 Z Dir - Pin D48 
 A Dir - Pin D28 

 X Enable - Pin D38 
 Y Enable - Pin A2 
 Z Enable - Pin A8 
 A Enable - Pin D24 

 X Limit Min - Pin D3 
 Y Limit Min - Pin D14 
 Z Limit Min - Pin D18 
 A Limit Min - Pin D42 

 X Limit Max - Pin D2 
 Y Limit Max - Pin D15 
 Z Limit Max - Pin D19 
 A Limit Max - Pin D40 


 | Axe | Step | Dir | Enable | Min | Max | 
 | X | A0 | A1 | D38 | D3 | D2 | 
 | Y | A6 | A7 | A2 | D14 | D15 | 
 | Z | D46 | D48 | A8 | D18 haut | D19 bas| 
 | T | D26 | D28 | D24 | D42 | D40 | 
 | _5_ | D36 | D34 | D30 | D44 | D59 A5 | 
 | _6_ | D49 | D51 | D53 | D57 A3 | D58 A4 | 

 h4. M62 - M65 Digital Output Control ports 

 M62 D16 
 M63 D17 
 M64 D23 
 M65 D25 

 h4. user-control CONTROLs (cycle start, reset, feed hold) input pins. 

 CONTROL_RESET    A9 
 CONTROL_FEED_HOLD A10 
 CONTROL_CYCLE_START A11 
 CONTROL_SAFETY_DOOR A12 

 Probe A15 

 SPINDLE_PWM_ON_D11 D11 
 SPINDLE_PWM_ON_D8 D8 
 SPINDLE_PWM_ON_D6 D6 

 h4. flood and mist coolant 

 COOLANT_FLOOD D10 
 COOLANT_MIST D9 

 spindle enable and spindle direction 

 SPINDLE_ENABLE D4 
 SPINDLE_DIRECTION D5 

 *Activation fin de course $21=1 dans GRBL* 

 h4. RAMPS 

 TX0 RX0 

 !clipboard-202303011533-x5grq.png! 
 !clipboard-202303021328-hbgya.png! 
 !clipboard-202111161107-c4k1x.png! 
 !clipboard-202110281149-o7xmm.png! 
 !GRBL_MEGA2560.png! 
 !clipboard-202111041029-zmpv6.png! 

 h4. mega 2560 pro  

 !clipboard-202309251452-wfe3v.png! 


 Gestion des erreur de GBRL 
 *error 9* locked utiliser commande $X 
 *error 22* definir vitesse F100 

 h4. DRV8825 avec moteurs pas a pas 

 Moteur 
 moteur nema17 17HS4401 200pas/tr 1.8° 
 moteur RS1805279 200pas/tr 1.8° 
 vis linéaire   
 T8 2mm/tr 
 M5 0.8mm/tr 
 avec microstep 1/1 
 T8 -> 100 pas/mm 
 M5 -> 250 pas/mm 
 avec microstep 1/32 
 T8 -> 3200 pas/mm 
 M5 -> 8000 pas/mm 

 

 h3. Config GRBL 

 h4. Direction 

 $3=0  	 Direction port invert, mask 

 h4. Hard limits 

 $5=0  	 Limit pins NOinvert, boolean 
 *$5=1*  	 Limit pins invert, boolean 
 $21=0  	 Hard limits OFF, boolean 
 *$21=1*  	 Hard limits ON, boolean 

 h4. Soft limits 

 $20=0  	 Soft limits OFF, boolean 
 *$20=1*  	 Soft limits ON, boolean 

 h4. Système métrique 

 $13=0  	 Report inches, boolean 
 *$13=1* 	 Report mm, boolean 

 

 h4. Homing 

 *$23 Homing dir invert, mask* 

 Par défaut, le cycle de homing passe par les étapes suivantes: 

     Axe Z 
         L’axe Z monte en vitesse rapide ($25) 
         Lorsque le fin de course Z est déclenché, Z s’arrête pour une courte période ($26), et recule d’une certaine distance ($27) 
         L’Axe Z va monter à nouveau lentement ($24) jusqu’à ce qu’il touche le fin de course à nouveau. 
         L’Axe Z recule d’une certaine distance ($27) 
     Axes X et Y 
         X et Y se déplacent tous les deux dans la direction du Homing, à vitesse rapide ($25) 
         Le premier Axe qui déclenche le fin de course s’arrête, et attends que l’autre Axe déclenche aussi. 
         Lorsque le second Axe touche le switch, les 2 axes reculent d’une distance pré-établie($27) 
         Les 2 axes X et Y vont se déplacer vers les fins de course à nouveau, lentement ($24), jusqu’à ce que les 2 switches soient à nouveau déclenchés 
         Les deux axes X et Y vont reculer d’une petite distance ($27) 


 *HOMING INIT LOCK* met Grbl dans un état d'alarme lors de la mise sous tension.  
 dans config.h ligne 154 
 // If homing is enabled, homing init lock sets Grbl into an alarm state upon power up. This forces 
 // the user to perform the homing cycle (or override the locks) before doing anything else. This is 
 // mainly a safety feature to remind the user to home, since position is unknown to Grbl. 
 #define HOMING_INIT_LOCK // Comment to disable 

 +*vitesse de l'axe Z trop rapide, et pull-off trop important*+ 

 $22=1  	 Homing cycle, boolean 
 $23=15  	 Homing dir invert, mask 15=LEFT,FRONT,DOWN,CCW 
 $24=1.000  	 Homing feed, mm/min 
 $25=5.000  	 Homing seek, mm/min 
 $26=250  	 Homing debounce, milliseconds 
 $27=1.000  	 Homing pull-off, mm 

 $14x      Homing feed, mm/min 
 $15x  	 Homing seek, mm/min 
 $16x      Homing pull-off, mm 

 

 h4. axe X 

 1/32 pas 
 vitesse 500 mm/min 
 $110=500 

 $100=3200 
 course 160mm 
 $130=160 

 h4. axe Y 

 1/32 pas 
 $101=3200 
 vitesse 500 mm/min 
 $121=500 
 course 178mm 
 $131=178 

 

 h4. axe Z 

 l'axe Z est non linéaire, la précision est obtenue mécaniquement par une came! 
 On ne peut pas utilisé les fonctions de GRBL pour piloté cet axe. 

 !clipboard-202402131112-ua98n.png! 

 TODO: 
 faire un code avec 
 attachInterrupt(digitalPinToInterrupt(pin), ISR, mode) 
 detachInterrupt(digitalPinToInterrupt(pin)) 

 course 0.518mm entre Z+ et Z-     


 vitesse F5 
 $102=3200 
 $112=5 vitesse mm/min 
 $122=1       Z Acceleration, max 1 mm/sec^2 
 $132=5 course en mm (il faut mettre pour ne pas déclencher ALARM:10) 

 utilisation du homing Z $HZ 
 mettre $23=15 pour avoir UP (a verifier cablage moteur ?) 
 mettre $23=11 ^pour avoir DOWN 

 !clipboard-202203291521-c4rgi.png! 
 réponse a la commande g01 z-1 f5 (déplacement de 1mm en descente a la vitesse de 5mm/min) chaque point est distant de 100ms 

 !clipboard-202203291532-lajvy.png! 
 réponse a la commande g01 z-0.5 f5 (déplacement de 0.5mm en descente a la vitesse de 5mm/min) chaque point est distant de 100ms 
 !clipboard-202203291536-xicje.png! 
 réponse a la commande g01 z0.5 f5 (déplacement de 0.5mm en monté a la vitesse de 5mm/min) chaque point est distant de 100ms 

 !clipboard-202204041458-rkqej.png! 
 déplacement g01 z-0.6 f5 depuis la position Z- jusqu’à la position Z+ 
 on trouve un décalage autour de 20µm! 

 !clipboard-202204121338-fq5ac.png! 
 homing Z $23=11 $122=1.000 $142=5.000 $152=5.000 $162=0.000 $HZ moteur Z en monté 

 !clipboard-202204121348-saeqz.png! 
 homing Z $23=11 $122=1.000 $142=5.000 $152=5.000 $162=0.000 $HZ moteur Z en descente 

 !clipboard-202204131039-zvdzy.png! 
 course axe Z, distance virtuelle 


 !clipboard-202204131522-sk0sh.png! 
 monté passage de Z- à Z+ avec correction COURSE(0.6mm) + MARGE (0.015mm) vitesse 100 mm/min 

 !clipboard-202204131523-thxix.png! 
 descente passage de Z+ à Z-    avec correction COURSE(0.6mm) + MARGE (0.015mm) vitesse 100 mm/min 

 !clipboard-202402051427-2udtg.png! 
 test ZDOWN avec firmware KON20240202 

 !clipboard-202402051429-krf5i.png! 
 test ZUP avec firmware KON20240202 

 

 h4. axe A (Theta) 

 vitesse F50 
 $102=4800 ° 
 $122=1       Acceleration, max 1 °/sec^2 

 course #22.5° (a finir) 

 h4. centre optique 

 X 71.800    mm 
 Y 108.500 mm 

 h4. $$ 

 $1=254 
 $2=0 
 $3=0 
 $4=0 
 $5=1 
 $6=0 
 $10=1 
 $11=0.020 
 $12=0.002 
 $13=0 
 $20=0 
 $21=0 
 $22=1 
 $23=11 
 $24=500.000 
 $25=500.000 
 $26=250 
 $27=1.000 
 $30=12000 
 $31=550 
 $32=0 
 $100=3200.000 
 $101=3200.000 
 $102=3200.000 
 $103=4800.000 
 $110=400.000 
 $111=400.000 
 $112=100.000 
 $113=100.000 
 $120=5.000 
 $121=5.000 
 $122=5.000 
 $123=5.000 
 $130=160.000 
 $131=178.000 
 $132=5.000 
 $133=22.500 
 $140=500.000 
 $141=500.000 
 $142=100.000 
 $143=100.000 
 $150=500.000 
 $151=500.000 
 $152=100.000 
 $153=100.000 
 $160=1.000 
 $161=1.000 
 $162=0.000 
 $163=1.000