Project

General

Profile

Wiki » History » Version 90

Frédéric Blanc, 2024-07-12 15:01

1 1 Frédéric Blanc
h1. Wiki
2
3 42 Frédéric Blanc
!{width: 30%}https://redmine.laas.fr/attachments/download/4815/Face%20AV%20PS.jpg!
4 43 Frédéric Blanc
5 42 Frédéric Blanc
!{width: 30%}https://redmine.laas.fr/attachments/download/4814/Face%20AR%20PS.jpg!
6
7 41 Frédéric Blanc
{{toc}}
8
9 11 Frédéric Blanc
h2. Modbus / RS485 isolated
10
11 25 Frédéric Blanc
!clipboard-202404091540-4btca.png!
12
13 50 Frédéric Blanc
https://arduino103.blogspot.com/2021/10/decoder-une-trame-rs485-loscilloscope.html
14
15 25 Frédéric Blanc
h3. non isoler
16 24 Frédéric Blanc
17
!clipboard-202404091414-fugem.png!
18
19 21 Frédéric Blanc
!clipboard-202404081517-wbjgq.png!
20
21 27 Frédéric Blanc
h4. Fusibles réarmables
22
23
!clipboard-202404091611-8b8z9.png!
24
25 23 Frédéric Blanc
h3. Texas Instruments ISOW14x2 Isolated RS-485 DC-DC Converter
26 22 Frédéric Blanc
27
!clipboard-202404081533-dzk67.png!
28
29 18 Frédéric Blanc
h3.  ANALOG DEVICES LTM2881CV-5#PBF
30
31 19 Frédéric Blanc
!clipboard-202404051942-kmfn5.jpg!
32
33 18 Frédéric Blanc
Transceiver, RS422, RS485, 20 Mbps, 1 Driver, 1 Récepteur, 4,5 à 5.5V, 0 à 70°C, LGA-32
34
35
Code Farnell 4023829
36
37
h3. ADM2865E Power Isolated, RS-485 Transceivers
38 12 Frédéric Blanc
39 1 Frédéric Blanc
!clipboard-202404041435-zyzea.png!
40 12 Frédéric Blanc
41 13 Frédéric Blanc
|Code Farnell|Référence Fabricant	|Fabricant / Description|
42 12 Frédéric Blanc
|4023816	|ADM2865EBRNZ	|ANALOG DEVICES  Transceiver, RS422, RS485, 25 Mbps, 1 Driver, 1 Récepteur, 3 à 5.5V, -40 à 105°C, WSOIC-28|
43
|1456395	|SM712.TCT	|SEMTECH  Diode TVS, SM, Bidirectionelle, 12 V, 26 V, SOT-23, 3 Broche(s)|
44
|1515786	|BLM15HD182SN1D	|MURATA  Perle de ferrite, 0402 [1005 Metric], 1.8 kohm, 200 mA, BLM15H, 2.2 ohm, ± 25%|
45
|1867958	|08053D106KAT2A	|KYOCERA AVX  Condensateur céramique multicouche CMS, 10 µF, 25 V, 0805 [Métrique 2012], ± 10%, X5R|
46
|2443238	|BLM18HE601SN1D	|MURATA  Perle de ferrite, 0603 [1608 Metric], 600 ohm, 800 mA, BLM18H, 0.25 ohm, ± 25%|
47 11 Frédéric Blanc
48 37 Frédéric Blanc
h3. Module de communication d'isolation, ADUM3201 + B0505XT TTL à RS485
49
50
!clipboard-202404231543-s8vft.png!
51
52
*Attention RX sur TX*
53
54 83 Frédéric Blanc
h3. DFR0845 
55
56
!clipboard-202407041533-yroi0.png!
57 90 Frédéric Blanc
!clipboard-202407121501-bz7ns.png!
58 83 Frédéric Blanc
Ce module de transfert de signal RS485 vers UART actif et isolé est livré avec des circuits de protection tels que l'isolation de puissance et le TVS. Compatible avec la plupart des contrôleurs principaux, il présente les caractéristiques d'une vitesse de communication rapide, de performances stables et fiables, d'une sécurité élevée, etc., et peut être appliqué à divers capteurs industriels, équipements de contrôle industriel ou applications nécessitant une conversion de signal RS485.
59
https://wiki.dfrobot.com/Gravity_Active_Isolated_RS485_to_UART_Signal_Converter_SKU_DFR0845
60
61 84 Frédéric Blanc
 N° Mouser :
62
426-DFR0845 
63
www.gotronic.fr
64 85 Frédéric Blanc
Code: 37411
65
https://fr.farnell.com
66 1 Frédéric Blanc
Code Commande :
67 88 Frédéric Blanc
3974134
68 84 Frédéric Blanc
69 28 Frédéric Blanc
h3. RS485 I2C
70
71
!clipboard-202404120929-wdgmq.png!
72
73 20 Frédéric Blanc
h2. XY5005E
74
75 40 Frédéric Blanc
com le port 4 broches JST 1.25 ne semble pas avoir de TX, ni de RX. Il n'y a pas non plus de menu pour le chois de l'adressage
76 20 Frédéric Blanc
77
!clipboard-202404081443-iygma.png!
78 39 Frédéric Blanc
!clipboard-202404241236-ulutn.png!
79 38 Frédéric Blanc
!clipboard-202404241234-m5crk.png!
80
81 14 Frédéric Blanc
h2. XY6015L Step-Down Regulated Power Supply
82 1 Frédéric Blanc
83
!clipboard-202403251011-lfrn1.png!
84
85 4 Frédéric Blanc
µC AT32F421  ARM® Cortex®-M4 core
86
Ctrl EG1163S BUCK DC-DC de Rectification synchrone 300kHz
87
MOS NCE82H140
88
89 81 Frédéric Blanc
h2. DPS5005
90
91
!clipboard-202406181357-wvt60.png!
92
93
94
95
Module d'alimentation à afficheur LCD réglable en tension de 0 à 50 Vcc et en intensité de 0 à 5 A. L'écran couleur de 1,44'' offre un affichage particulièrement détaillé et complet des informations.
96
97
https://www.gotronic.fr/art-alimentation-programmable-dps5005-29294.htm
98
99 86 Frédéric Blanc
h3. modification port com
100
101
La vitesse de communication par défaut du port série DPS5005 est de 9 600 bauds, mais vous pouvez la modifier en alimentant l'alimentation tout en maintenant le bouton V/M1 enfoncé. Lorsque la modification est effectuée, appuyez deux fois sur le bouton « set » pour enregistrer la nouvelle configuration.
102
103 87 Frédéric Blanc
h3. Brochage port com
104
105
!clipboard-202407121448-7reos.png!
106
107
108 81 Frédéric Blanc
h2. DPH5005
109
110
!clipboard-202406181358-4or4r.png!
111
112
Module d'alimentation à afficheur LCD 1,44" réglable en tension de 0 à 50 Vcc et en intensité de 0 à 5 A. Ce module délivre un signal de sortie haute résolution réglable par paliers de 10 mV et de 1 mA.
113
114
https://www.gotronic.fr/art-alimentation-programmable-dph5005-31537.htm
115
116 31 Frédéric Blanc
h3. Modbus
117
118 1 Frédéric Blanc
!clipboard-202404121322-qk0l1.png!
119 32 Frédéric Blanc
120 53 Frédéric Blanc
voir documentation document:"protocol -english translation V1.2"
121
122 64 Frédéric Blanc
|_.function code|_.Definition|_.Operation (binary)|
123 52 Frédéric Blanc
|0x03|Read register data|Read data from one or more registers|
124
|0x06|Write a single register|Write a set of binary data to a single register|
125
|0x10|Write multiple registers|Write multiple sets of binary data to multiple registers|
126
127 61 Frédéric Blanc
|\5=. *0x03 Read the function of the host format* |
128 57 Frédéric Blanc
|address code|function code|Register start address |Number of register
129
 addresses n (1 ~ 32)|CRC Check code|
130 54 Frédéric Blanc
|1 byte|1 byte|2 byte|2 byte|2 byte|
131
132 62 Frédéric Blanc
|\5=. *0x03 Read function Slave returns format*|
133
|address code|function code|Returns the number of bytes 2 * n|Register data|CRC Check code|
134
|1 byte|1 byte|1 byte|2*n Bytes|2 byte|
135 52 Frédéric Blanc
136 63 Frédéric Blanc
|\5=. *0x06 Write a single register function in host format*|
137
|address code|function code|Register address|Register data|CRC Check code|
138 1 Frédéric Blanc
|1 byte|1 byte|2 byte|2 byte|2 byte|
139 64 Frédéric Blanc
140 65 Frédéric Blanc
|\5=. *0x06 Write a single register function from the machine to return the format*|
141 64 Frédéric Blanc
|address code|function code|Register address|Register data|CRC Check code|
142
|1 byte|1 byte|2 byte|2 byte|2 byte|
143
144 68 Frédéric Blanc
|\6=. *0x10 Write function host format*|
145 67 Frédéric Blanc
|address code|function code|Register start address|Number of register addresses
146
n (1 ~ 32)|Write the number of bytes 2 * n|Register data|CRC Check code|
147 66 Frédéric Blanc
|1 byte|1 byte|2 byte|2 byte|1 byte|2*n byte|2 byte|
148
149
|\5=. *0x10 Write function slave return format*|
150 67 Frédéric Blanc
|address code|function code|Register start address|Number of register addresses
151 66 Frédéric Blanc
n (1 ~ 32)|CRC Check code|
152
|1 byte|1 byte|2 byte|2 byte|2 byte|
153 63 Frédéric Blanc
154 69 Frédéric Blanc
Protocol register description (single register address data for double-byte data)
155 70 Frédéric Blanc
156 76 Frédéric Blanc
|name|Description|number of bytes|Decimal point|unit|Read and write|Register address|dps_modbus.py|
157
|U-SET|Voltage setting|2|2|V|R/W|0x0000|voltage_set|
158
|I-SET|Current setting|2|2|A|R/W|0x0001|current_set|
159
|UOUT|Output voltage display value|2|2|V|R|0x0002|voltage|
160
|IOUT|Output current display value|2|2|A|R|0x0003|current|
161
|POWER|Output power display value|2|2|W|R|0x0004|power|
162
|UIN|Input voltage display value|2|2|V|R|0x0005|voltage_in|
163
|LOCK|Key lock|2|0|-|R/W|0x0006|lock|
164
|PROTECT|Protection state|2|0|-|R|0x0007|protect|
165
|CVCC|Constant voltage constant current state|2|0|-|R|0x0008|cv_cc|
166
|ONOFF|Switch output|2|0|-|R/W|0x0009|onoff|
167
|B_LED|Backlight brightness level|2|0|-|R/W|0x000A|b_led|
168
|MODEL|Product number|2|0|-|R|0x000B|model|
169
|VERSON|Firmware version number|2|0|-|R|0x000C|version|
170
|EXTRACT_M|Quickly bring up data sets|2|0|-|W|0x0023|extract_m|
171
|U-SET|Voltage setting|2|2|V|R/W|0x0050|voltage_set2|
172
|I-SET|Current setting|2|3|A|R/W|0x0051|current_set2|
173
|S-OVP|Overvoltage protection|2|2|V|R/W|0x0052|s_ovp|
174
|S-OCP|Overcurrent protection value|2|3|A|R/W|0x0053|s_ocp|
175
|S-OPP|Over power protection value|2|1、2|W|R/W|0x0054|s_opp|
176
|B-LED|Backlight brightness level|2|0|-|R/W|0x0055|b_led2|
177
|M-PRE|The data is called to update the output|2|0|-|R/W|0x0056|m_pre|
178
|S-INI|Power on the output switch|2|2|-|R/W|0x0057|s_ini|
179 75 Frédéric Blanc
180 76 Frédéric Blanc
h3. dps_modbus.py
181 69 Frédéric Blanc
182 79 Frédéric Blanc
|commande|Description|
183 78 Frédéric Blanc
|voltage_set|Voltage setting|
184
|current_set|Current setting|
185
|voltage|Output voltage display value|
186
|current|Output current display value|
187
|power|Output power display value|
188
|voltage_in|Input voltage display value|
189
|lock|Key lock|
190
|protect|Protection state|
191
|cv_cc|Constant voltage constant current state|
192
|onoff|Switch output|
193
|b_led|Backlight brightness level|
194
|model|Product number|
195
|version|Firmware version number|
196
|extract_m|Quickly bring up data sets|
197
|voltage_set2|Voltage setting|
198
|current_set2|Current setting|
199
|s_ovp|Overvoltage protection|
200
|s_ocp|Overcurrent protection value|
201
|s_opp|Over power protection value|
202
|b_led2|Backlight brightness level|
203
|m_pre|The data is called to update the output|
204
|s_ini|Power on the output switch|
205 77 Frédéric Blanc
|read_all|Read data as a block, much faster than individual reads|
206
|write_voltage_current|write voltage & current as a block|
207
|write_all|write block|
208
209
210 47 Frédéric Blanc
/dev/ttyACM0 ou /dev/ttyUSB0
211 32 Frédéric Blanc
baud rate *115200*
212 31 Frédéric Blanc
213 1 Frédéric Blanc
Slave Address: 1..247 ( *0: broadcast* )
214 31 Frédéric Blanc
Function code: see later
215
Data: 0..252 byte(s)
216 33 Frédéric Blanc
*CRC16-MODBUS* : see https://crccalc.com/ for code.
217 48 Frédéric Blanc
https://github.com/LacobusVentura/MODBUS-CRC16
218 31 Frédéric Blanc
219 1 Frédéric Blanc
220 34 Frédéric Blanc
h3. test commande
221
222 1 Frédéric Blanc
223 46 Frédéric Blanc
224 45 Frédéric Blanc
sur /dev/ttyACM0
225 1 Frédéric Blanc
226 46 Frédéric Blanc
Broadcast Power ON
227 1 Frédéric Blanc
<pre><code class="shell">
228 35 Frédéric Blanc
echo -ne "\x00\x06\x00\x12\x00\x01\xE9\xDE" > /dev/ttyACM0
229 34 Frédéric Blanc
</code></pre>
230
231 36 Frédéric Blanc
Broadcast Power OFF
232
<pre><code class="shell">
233
echo -ne "\x00\x06\x00\x12\x00\x00\x28\x1E" > /dev/ttyACM0
234
</code></pre>
235 1 Frédéric Blanc
236 45 Frédéric Blanc
sur /dev/ttyUSB0
237 1 Frédéric Blanc
238 46 Frédéric Blanc
Broadcast Power ON
239 45 Frédéric Blanc
<pre><code class="shell">
240
echo -ne "\x00\x06\x00\x12\x00\x01\xE9\xDE" > /dev/ttyUSB0
241
</code></pre>
242
243
Broadcast Power OFF
244
<pre><code class="shell">
245
echo -ne "\x00\x06\x00\x12\x00\x00\x28\x1E" > /dev/ttyUSB0
246
</code></pre>
247 36 Frédéric Blanc
248 30 Frédéric Blanc
h3. notice
249 15 Frédéric Blanc
250
presser [SW] pendant 2s pour accéder aux paramètres 
251
!clipboard-202404041503-e5ifh.png!
252
253 6 Frédéric Blanc
h2. GUI Python
254
255 9 Frédéric Blanc
h3. venv — Création d'environnements virtuels
256 6 Frédéric Blanc
257
<pre><code class="shell">
258 8 Frédéric Blanc
$ python3 -m venv venv
259 6 Frédéric Blanc
</code></pre>
260
261
Pour activer l'environnement, exécutez
262
263
<pre><code class="shell">
264
source venv/bin/activate
265
</code></pre>
266
267 7 Frédéric Blanc
<pre><code class="shell">
268
. venv/bin/activate
269
</code></pre>
270
271 51 Frédéric Blanc
sous Windows
272
<pre><code class="shell">
273
env\Scripts\activate.bat
274
</code></pre>
275
276 9 Frédéric Blanc
Vous devrez « quitter » ou « désactiver » votre environnement virtuel à l'aide de la commande 
277 6 Frédéric Blanc
278
<pre><code class="shell">
279
deactivate
280
</code></pre>
281
282
283
284 1 Frédéric Blanc
https://docs.python.org/fr/3/library/venv.html
285
286 16 Frédéric Blanc
h3. pyqt5
287
288
<pre><code class="shell">
289
pip3 install pyqt5 --config-settings --confirm-license= --verbose
290
</code></pre>
291
292 17 Frédéric Blanc
https://stackoverflow.com/questions/73714829/pip-install-pyqt5-it-cannot-go-on
293 16 Frédéric Blanc
294 9 Frédéric Blanc
h3. XY6015L_pyGUI
295
296 44 Frédéric Blanc
lancement de l'interface
297
298
<pre><code class="python">
299
python dps_GUI_program.py
300
</code></pre>
301
302 9 Frédéric Blanc
!clipboard-202404041117-w53xm.png!
303
304
configuration du port com
305
306
le port série peut être corrigé en modifiant le paramètre "port_set" dans "dps5005_limits.ini".
307
308
309
<pre><code class="shell">
310
[SectionZero]
311
The parameters below limit the code from incorrectly transmitting extreme values entered by the user:
312
if threshold exceeded value defaults to zero:
313
This file may be adapted for other versions of 'DPSxxxx' power supplies:
314
315
[SectionOne]
316
#leave empty "" for automatic port scanning or set serial port e.g. "/dev/cu.wchusbserial1410" or "/dev/ttyUSB0":
317
port_set: "/dev/ttyACM0"	#
318
319
#The parameters below limit the code from incorrectly transmitting extreme values entered by the user:
320 1 Frédéric Blanc
#if threshold exceeded value defaults to zero:
321 10 Frédéric Blanc
...
322 9 Frédéric Blanc
</code></pre>
323
324
h2. Sources
325 5 Frédéric Blanc
326 82 Frédéric Blanc
https://profimaxblog.ru/dps_update/
327 26 Frédéric Blanc
https://www.circuitstate.com/tutorials/what-is-rs-485-how-to-use-max485-with-arduino-for-reliable-long-distance-serial-communication/
328 29 Frédéric Blanc
http://xj900diversion.free.fr/bus/I2C%20-%20RS-485%20adapter.htm
329 5 Frédéric Blanc
https://github.com/AntaresAdroit/RDTech_PS_Comm
330
https://github.com/lambcutlet/DPS5005_pyGUI
331
https://github.com/kbs3056/XY6015L_pyGUI