Project

General

Profile

Wiki » History » Version 94

Frédéric Blanc, 2024-07-17 16:42

1 1 Frédéric Blanc
h1. Wiki
2
3 42 Frédéric Blanc
!{width: 30%}https://redmine.laas.fr/attachments/download/4815/Face%20AV%20PS.jpg!
4 43 Frédéric Blanc
5 42 Frédéric Blanc
!{width: 30%}https://redmine.laas.fr/attachments/download/4814/Face%20AR%20PS.jpg!
6
7 41 Frédéric Blanc
{{toc}}
8
9 11 Frédéric Blanc
h2. Modbus / RS485 isolated
10
11 25 Frédéric Blanc
!clipboard-202404091540-4btca.png!
12
13 50 Frédéric Blanc
https://arduino103.blogspot.com/2021/10/decoder-une-trame-rs485-loscilloscope.html
14
15 25 Frédéric Blanc
h3. non isoler
16 24 Frédéric Blanc
17
!clipboard-202404091414-fugem.png!
18
19 21 Frédéric Blanc
!clipboard-202404081517-wbjgq.png!
20
21 27 Frédéric Blanc
h4. Fusibles réarmables
22
23
!clipboard-202404091611-8b8z9.png!
24
25 23 Frédéric Blanc
h3. Texas Instruments ISOW14x2 Isolated RS-485 DC-DC Converter
26 22 Frédéric Blanc
27
!clipboard-202404081533-dzk67.png!
28
29 18 Frédéric Blanc
h3.  ANALOG DEVICES LTM2881CV-5#PBF
30
31 19 Frédéric Blanc
!clipboard-202404051942-kmfn5.jpg!
32
33 18 Frédéric Blanc
Transceiver, RS422, RS485, 20 Mbps, 1 Driver, 1 Récepteur, 4,5 à 5.5V, 0 à 70°C, LGA-32
34
35
Code Farnell 4023829
36
37
h3. ADM2865E Power Isolated, RS-485 Transceivers
38 12 Frédéric Blanc
39 1 Frédéric Blanc
!clipboard-202404041435-zyzea.png!
40 12 Frédéric Blanc
41 13 Frédéric Blanc
|Code Farnell|Référence Fabricant	|Fabricant / Description|
42 12 Frédéric Blanc
|4023816	|ADM2865EBRNZ	|ANALOG DEVICES  Transceiver, RS422, RS485, 25 Mbps, 1 Driver, 1 Récepteur, 3 à 5.5V, -40 à 105°C, WSOIC-28|
43
|1456395	|SM712.TCT	|SEMTECH  Diode TVS, SM, Bidirectionelle, 12 V, 26 V, SOT-23, 3 Broche(s)|
44
|1515786	|BLM15HD182SN1D	|MURATA  Perle de ferrite, 0402 [1005 Metric], 1.8 kohm, 200 mA, BLM15H, 2.2 ohm, ± 25%|
45
|1867958	|08053D106KAT2A	|KYOCERA AVX  Condensateur céramique multicouche CMS, 10 µF, 25 V, 0805 [Métrique 2012], ± 10%, X5R|
46
|2443238	|BLM18HE601SN1D	|MURATA  Perle de ferrite, 0603 [1608 Metric], 600 ohm, 800 mA, BLM18H, 0.25 ohm, ± 25%|
47 11 Frédéric Blanc
48 37 Frédéric Blanc
h3. Module de communication d'isolation, ADUM3201 + B0505XT TTL à RS485
49
50
!clipboard-202404231543-s8vft.png!
51
52
*Attention RX sur TX*
53
54 83 Frédéric Blanc
h3. DFR0845 
55
56
!clipboard-202407041533-yroi0.png!
57 90 Frédéric Blanc
!clipboard-202407121501-bz7ns.png!
58 83 Frédéric Blanc
Ce module de transfert de signal RS485 vers UART actif et isolé est livré avec des circuits de protection tels que l'isolation de puissance et le TVS. Compatible avec la plupart des contrôleurs principaux, il présente les caractéristiques d'une vitesse de communication rapide, de performances stables et fiables, d'une sécurité élevée, etc., et peut être appliqué à divers capteurs industriels, équipements de contrôle industriel ou applications nécessitant une conversion de signal RS485.
59
https://wiki.dfrobot.com/Gravity_Active_Isolated_RS485_to_UART_Signal_Converter_SKU_DFR0845
60
61 84 Frédéric Blanc
 N° Mouser :
62
426-DFR0845 
63
www.gotronic.fr
64 85 Frédéric Blanc
Code: 37411
65
https://fr.farnell.com
66 1 Frédéric Blanc
Code Commande :
67 88 Frédéric Blanc
3974134
68 84 Frédéric Blanc
69 28 Frédéric Blanc
h3. RS485 I2C
70
71
!clipboard-202404120929-wdgmq.png!
72
73 20 Frédéric Blanc
h2. XY5005E
74
75 40 Frédéric Blanc
com le port 4 broches JST 1.25 ne semble pas avoir de TX, ni de RX. Il n'y a pas non plus de menu pour le chois de l'adressage
76 20 Frédéric Blanc
77
!clipboard-202404081443-iygma.png!
78 39 Frédéric Blanc
!clipboard-202404241236-ulutn.png!
79 38 Frédéric Blanc
!clipboard-202404241234-m5crk.png!
80
81 14 Frédéric Blanc
h2. XY6015L Step-Down Regulated Power Supply
82 1 Frédéric Blanc
83
!clipboard-202403251011-lfrn1.png!
84
85 4 Frédéric Blanc
µC AT32F421  ARM® Cortex®-M4 core
86
Ctrl EG1163S BUCK DC-DC de Rectification synchrone 300kHz
87
MOS NCE82H140
88
89 81 Frédéric Blanc
h2. DPS5005
90
91
!clipboard-202406181357-wvt60.png!
92
93
94
95
Module d'alimentation à afficheur LCD réglable en tension de 0 à 50 Vcc et en intensité de 0 à 5 A. L'écran couleur de 1,44'' offre un affichage particulièrement détaillé et complet des informations.
96
97
https://www.gotronic.fr/art-alimentation-programmable-dps5005-29294.htm
98
99 86 Frédéric Blanc
h3. modification port com
100
101
La vitesse de communication par défaut du port série DPS5005 est de 9 600 bauds, mais vous pouvez la modifier en alimentant l'alimentation tout en maintenant le bouton V/M1 enfoncé. Lorsque la modification est effectuée, appuyez deux fois sur le bouton « set » pour enregistrer la nouvelle configuration.
102
103 91 Frédéric Blanc
h3. Firmware alternatif
104
105
https://github.com/kanflo/opendps
106 92 Frédéric Blanc
https://redmine.laas.fr/attachments/4885
107 91 Frédéric Blanc
108 87 Frédéric Blanc
h3. Brochage port com
109
110
!clipboard-202407121448-7reos.png!
111
112
113 81 Frédéric Blanc
h2. DPH5005
114
115
!clipboard-202406181358-4or4r.png!
116
117
Module d'alimentation à afficheur LCD 1,44" réglable en tension de 0 à 50 Vcc et en intensité de 0 à 5 A. Ce module délivre un signal de sortie haute résolution réglable par paliers de 10 mV et de 1 mA.
118
119
https://www.gotronic.fr/art-alimentation-programmable-dph5005-31537.htm
120
121 31 Frédéric Blanc
h3. Modbus
122
123 1 Frédéric Blanc
!clipboard-202404121322-qk0l1.png!
124 32 Frédéric Blanc
125 53 Frédéric Blanc
voir documentation document:"protocol -english translation V1.2"
126
127 64 Frédéric Blanc
|_.function code|_.Definition|_.Operation (binary)|
128 52 Frédéric Blanc
|0x03|Read register data|Read data from one or more registers|
129
|0x06|Write a single register|Write a set of binary data to a single register|
130
|0x10|Write multiple registers|Write multiple sets of binary data to multiple registers|
131
132 61 Frédéric Blanc
|\5=. *0x03 Read the function of the host format* |
133 57 Frédéric Blanc
|address code|function code|Register start address |Number of register
134
 addresses n (1 ~ 32)|CRC Check code|
135 54 Frédéric Blanc
|1 byte|1 byte|2 byte|2 byte|2 byte|
136
137 62 Frédéric Blanc
|\5=. *0x03 Read function Slave returns format*|
138
|address code|function code|Returns the number of bytes 2 * n|Register data|CRC Check code|
139
|1 byte|1 byte|1 byte|2*n Bytes|2 byte|
140 52 Frédéric Blanc
141 63 Frédéric Blanc
|\5=. *0x06 Write a single register function in host format*|
142
|address code|function code|Register address|Register data|CRC Check code|
143 1 Frédéric Blanc
|1 byte|1 byte|2 byte|2 byte|2 byte|
144 64 Frédéric Blanc
145 65 Frédéric Blanc
|\5=. *0x06 Write a single register function from the machine to return the format*|
146 64 Frédéric Blanc
|address code|function code|Register address|Register data|CRC Check code|
147
|1 byte|1 byte|2 byte|2 byte|2 byte|
148
149 68 Frédéric Blanc
|\6=. *0x10 Write function host format*|
150 67 Frédéric Blanc
|address code|function code|Register start address|Number of register addresses
151
n (1 ~ 32)|Write the number of bytes 2 * n|Register data|CRC Check code|
152 66 Frédéric Blanc
|1 byte|1 byte|2 byte|2 byte|1 byte|2*n byte|2 byte|
153
154
|\5=. *0x10 Write function slave return format*|
155 67 Frédéric Blanc
|address code|function code|Register start address|Number of register addresses
156 66 Frédéric Blanc
n (1 ~ 32)|CRC Check code|
157
|1 byte|1 byte|2 byte|2 byte|2 byte|
158 63 Frédéric Blanc
159 69 Frédéric Blanc
Protocol register description (single register address data for double-byte data)
160 70 Frédéric Blanc
161 76 Frédéric Blanc
|name|Description|number of bytes|Decimal point|unit|Read and write|Register address|dps_modbus.py|
162
|U-SET|Voltage setting|2|2|V|R/W|0x0000|voltage_set|
163
|I-SET|Current setting|2|2|A|R/W|0x0001|current_set|
164
|UOUT|Output voltage display value|2|2|V|R|0x0002|voltage|
165
|IOUT|Output current display value|2|2|A|R|0x0003|current|
166
|POWER|Output power display value|2|2|W|R|0x0004|power|
167
|UIN|Input voltage display value|2|2|V|R|0x0005|voltage_in|
168
|LOCK|Key lock|2|0|-|R/W|0x0006|lock|
169
|PROTECT|Protection state|2|0|-|R|0x0007|protect|
170
|CVCC|Constant voltage constant current state|2|0|-|R|0x0008|cv_cc|
171
|ONOFF|Switch output|2|0|-|R/W|0x0009|onoff|
172
|B_LED|Backlight brightness level|2|0|-|R/W|0x000A|b_led|
173
|MODEL|Product number|2|0|-|R|0x000B|model|
174
|VERSON|Firmware version number|2|0|-|R|0x000C|version|
175
|EXTRACT_M|Quickly bring up data sets|2|0|-|W|0x0023|extract_m|
176
|U-SET|Voltage setting|2|2|V|R/W|0x0050|voltage_set2|
177
|I-SET|Current setting|2|3|A|R/W|0x0051|current_set2|
178
|S-OVP|Overvoltage protection|2|2|V|R/W|0x0052|s_ovp|
179
|S-OCP|Overcurrent protection value|2|3|A|R/W|0x0053|s_ocp|
180
|S-OPP|Over power protection value|2|1、2|W|R/W|0x0054|s_opp|
181
|B-LED|Backlight brightness level|2|0|-|R/W|0x0055|b_led2|
182
|M-PRE|The data is called to update the output|2|0|-|R/W|0x0056|m_pre|
183
|S-INI|Power on the output switch|2|2|-|R/W|0x0057|s_ini|
184 75 Frédéric Blanc
185 76 Frédéric Blanc
h3. dps_modbus.py
186 69 Frédéric Blanc
187 79 Frédéric Blanc
|commande|Description|
188 78 Frédéric Blanc
|voltage_set|Voltage setting|
189
|current_set|Current setting|
190
|voltage|Output voltage display value|
191
|current|Output current display value|
192
|power|Output power display value|
193
|voltage_in|Input voltage display value|
194
|lock|Key lock|
195
|protect|Protection state|
196
|cv_cc|Constant voltage constant current state|
197
|onoff|Switch output|
198
|b_led|Backlight brightness level|
199
|model|Product number|
200
|version|Firmware version number|
201
|extract_m|Quickly bring up data sets|
202
|voltage_set2|Voltage setting|
203
|current_set2|Current setting|
204
|s_ovp|Overvoltage protection|
205
|s_ocp|Overcurrent protection value|
206
|s_opp|Over power protection value|
207
|b_led2|Backlight brightness level|
208
|m_pre|The data is called to update the output|
209
|s_ini|Power on the output switch|
210 77 Frédéric Blanc
|read_all|Read data as a block, much faster than individual reads|
211
|write_voltage_current|write voltage & current as a block|
212
|write_all|write block|
213
214
215 47 Frédéric Blanc
/dev/ttyACM0 ou /dev/ttyUSB0
216 32 Frédéric Blanc
baud rate *115200*
217 31 Frédéric Blanc
218 1 Frédéric Blanc
Slave Address: 1..247 ( *0: broadcast* )
219 31 Frédéric Blanc
Function code: see later
220
Data: 0..252 byte(s)
221 33 Frédéric Blanc
*CRC16-MODBUS* : see https://crccalc.com/ for code.
222 48 Frédéric Blanc
https://github.com/LacobusVentura/MODBUS-CRC16
223 31 Frédéric Blanc
224 1 Frédéric Blanc
225 34 Frédéric Blanc
h3. test commande
226
227 1 Frédéric Blanc
228 46 Frédéric Blanc
229 45 Frédéric Blanc
sur /dev/ttyACM0
230 1 Frédéric Blanc
231 46 Frédéric Blanc
Broadcast Power ON
232 1 Frédéric Blanc
<pre><code class="shell">
233 35 Frédéric Blanc
echo -ne "\x00\x06\x00\x12\x00\x01\xE9\xDE" > /dev/ttyACM0
234 34 Frédéric Blanc
</code></pre>
235
236 36 Frédéric Blanc
Broadcast Power OFF
237
<pre><code class="shell">
238
echo -ne "\x00\x06\x00\x12\x00\x00\x28\x1E" > /dev/ttyACM0
239
</code></pre>
240 1 Frédéric Blanc
241 45 Frédéric Blanc
sur /dev/ttyUSB0
242 1 Frédéric Blanc
243 46 Frédéric Blanc
Broadcast Power ON
244 45 Frédéric Blanc
<pre><code class="shell">
245
echo -ne "\x00\x06\x00\x12\x00\x01\xE9\xDE" > /dev/ttyUSB0
246
</code></pre>
247
248
Broadcast Power OFF
249
<pre><code class="shell">
250
echo -ne "\x00\x06\x00\x12\x00\x00\x28\x1E" > /dev/ttyUSB0
251
</code></pre>
252 36 Frédéric Blanc
253 30 Frédéric Blanc
h3. notice
254 15 Frédéric Blanc
255
presser [SW] pendant 2s pour accéder aux paramètres 
256
!clipboard-202404041503-e5ifh.png!
257
258 6 Frédéric Blanc
h2. GUI Python
259
260 9 Frédéric Blanc
h3. venv — Création d'environnements virtuels
261 6 Frédéric Blanc
262
<pre><code class="shell">
263 8 Frédéric Blanc
$ python3 -m venv venv
264 6 Frédéric Blanc
</code></pre>
265
266
Pour activer l'environnement, exécutez
267
268
<pre><code class="shell">
269
source venv/bin/activate
270
</code></pre>
271
272 7 Frédéric Blanc
<pre><code class="shell">
273
. venv/bin/activate
274
</code></pre>
275
276 51 Frédéric Blanc
sous Windows
277
<pre><code class="shell">
278
env\Scripts\activate.bat
279
</code></pre>
280
281 9 Frédéric Blanc
Vous devrez « quitter » ou « désactiver » votre environnement virtuel à l'aide de la commande 
282 6 Frédéric Blanc
283
<pre><code class="shell">
284
deactivate
285
</code></pre>
286
287
288
289 1 Frédéric Blanc
https://docs.python.org/fr/3/library/venv.html
290
291 16 Frédéric Blanc
h3. pyqt5
292
293
<pre><code class="shell">
294
pip3 install pyqt5 --config-settings --confirm-license= --verbose
295
</code></pre>
296
297 17 Frédéric Blanc
https://stackoverflow.com/questions/73714829/pip-install-pyqt5-it-cannot-go-on
298 16 Frédéric Blanc
299 9 Frédéric Blanc
h3. XY6015L_pyGUI
300
301 44 Frédéric Blanc
lancement de l'interface
302
303
<pre><code class="python">
304
python dps_GUI_program.py
305
</code></pre>
306
307 9 Frédéric Blanc
!clipboard-202404041117-w53xm.png!
308
309
configuration du port com
310
311
le port série peut être corrigé en modifiant le paramètre "port_set" dans "dps5005_limits.ini".
312
313
314
<pre><code class="shell">
315
[SectionZero]
316
The parameters below limit the code from incorrectly transmitting extreme values entered by the user:
317
if threshold exceeded value defaults to zero:
318
This file may be adapted for other versions of 'DPSxxxx' power supplies:
319
320
[SectionOne]
321
#leave empty "" for automatic port scanning or set serial port e.g. "/dev/cu.wchusbserial1410" or "/dev/ttyUSB0":
322
port_set: "/dev/ttyACM0"	#
323
324
#The parameters below limit the code from incorrectly transmitting extreme values entered by the user:
325 1 Frédéric Blanc
#if threshold exceeded value defaults to zero:
326 10 Frédéric Blanc
...
327 9 Frédéric Blanc
</code></pre>
328
329 93 Frédéric Blanc
h2. SCPI
330
331 94 Frédéric Blanc
h3. SCPI parser
332
333
À propos de l'analyseur SCPI
334
335
La bibliothèque SCPI Parser vise à fournir une capacité d'analyse des commandes SCPI côté instrument. Toutes les commandes sont définies par leurs modèles, par exemple : "STATus:QUEStionable:EVENt?".
336
337
Les codes sources sont publiés avec une licence BSD simplifiée open source.
338
339
La bibliothèque d'analyseurs SCPI est basée sur ces normes:
340
SCPI-99
341
IEEE 488.2-2004
342
343
344 93 Frédéric Blanc
https://github.com/j123b567/scpi-parser
345
346 9 Frédéric Blanc
h2. Sources
347 5 Frédéric Blanc
348 82 Frédéric Blanc
https://profimaxblog.ru/dps_update/
349 26 Frédéric Blanc
https://www.circuitstate.com/tutorials/what-is-rs-485-how-to-use-max485-with-arduino-for-reliable-long-distance-serial-communication/
350 29 Frédéric Blanc
http://xj900diversion.free.fr/bus/I2C%20-%20RS-485%20adapter.htm
351 5 Frédéric Blanc
https://github.com/AntaresAdroit/RDTech_PS_Comm
352
https://github.com/lambcutlet/DPS5005_pyGUI
353
https://github.com/kbs3056/XY6015L_pyGUI